4-20mA 3 Phase 4 Wire Electrical Isolation Sensor

4-20mA 3 Phase 4 Wire Electrical Isolation Sensor

This product uses a special isolation module to measure the AC voltage in the power grid and circuit in real time and convert it into a standard DC voltage (Uz) output. This product assembles the contents of three single-phase circuits into one product casing. It has the characteristics of small...
Send Inquiry
Description
Technical Parameters

WB3V412U01(4-20mA 3 Phase 4 Wire Electrical Isolation Sensor) uses a special isolation module to measure the AC voltage in the power grid and circuit in real time and convert it into a standard DC voltage (Uz) output. 4-20mA 3 Phase 4 Wire Electrical Isolation Sensor assembles the contents of three single-phase circuits into one product casing. It has the advantages of small size, high precision, high isolation, wide frequency response, low drift, low power consumption and wide temperature range. 4-20mA 3 Phase 4 Wire Electrical Isolation Sensor adopts a card-mounted structure, compact structure and convenient installation. It is suitable for real-time detection of 3-phase 4-wire circuit of power system.


Advantages:

   27000 square meters non-dust workshop,

   30 years’ experience,

   6 years' application in high speed railway,

   ISO, EMC, ETC certificated.

 

Applications:

   Intelligent low-voltage power distribution system;

   DC power screen, box substation;

   Temperature and fire monitoring for transformer, fire monitoring for cable;

   High-voltage switchgear fiber optic temperature measurement system;

   Transformer contact monitoring.


Hot Tags: 4-20mA 3 Phase 4 Wire Electrical Isolation Sensor, China, suppliers, factory, price, 10V 500V Input AC Voltage Transducer, 0 20mA Output AC Voltage Transducer, Voltage Sensor 60V, Voltage Transducer 60V, Voltage Sensor 30V, 10V 500V Input Electrical Isolation Transducer

  1. Input: 0-500V;

  2. Output: 0-10V;

  3. Accuracy level: 0.5;

  4. Linear range: 0% to 120% nominal input;

  5. Frequency response: 25Hz ~ 5kHz;

  6. Response time: 300ms;

  7. Input impedance: Ri=Ux×1kΩ/V (Ux represents the measured input voltage);

  8. Overload capability: 2 times the nominal input voltage value;

  9. Load capacity: 5mA;

  10. Static current: 12mA;

  11. Auxiliary power supply: 12V or 24V;

  12. Isolation withstand voltage: >DC 2.5kV, 1min;

  13. Output ripple: <6mV (effective value);

  14. Ambient temperature: 0 ° C ~ 50 ° C;

  15. Temperature drift: 250 × 10-6 / °C.