DC Current Sensor 4 to 20mA Output

DC Current Sensor 4 to 20mA Output

WBI344U01-S converts DC input current into a load independent output signal DC(0)4-20mA. It has adopted electromagnetic isolation principle for real time measurement of AC current from electric net or electric circuit.
Send Inquiry
Description
Technical Parameters

WBI344U01-S (DC Current Sensor 4–20 mA Output) converts DC input current into a load-independent DC output signal of 0(4)–20 mA.

 

The DC Current Sensor 4–20 mA Output adopts the electromagnetic isolation principle for real-time measurement of DC current from a power grid or electrical circuit.

 

The generated magnetic flux is concentrated in the magnetic circuit by a high-quality magnetic core. The Hall element is fixed in a small air gap, where the magnetic flux is detected linearly. The Hall voltage output from the 4–20 mA DC current sensor is processed by a dedicated circuit. The secondary side then outputs a corresponding signal consistent with the primary-side waveform, accurately reflecting changes in the primary current.

 

Note:
Testing must be carried out under the following conditions:

Auxiliary power: 24V ±5%, ripple ≤5 mV
Ambient temperature: 25℃ ±5℃
Relative humidity: RH (45–75)%

Accuracy of the signal power source instrument: 0.05

3

Advantages:
High precision
High isolation
Low power consumption
Low drift
Wide temperature range
Strong anti-interference capability
Strong operational capability
Wide operating power range

 

Applications:
Current measurement
Automatic monitoring and control
Electrical signal monitoring and modulation
Data acquisition

 

Hot Tags: DC Current Sensor 4 to 20mA Output, China, suppliers, factory, price, DC Current Transducer 4 20mA Output, DC Current Transducer Module, 0 5V Output, DC Current Transducer, 0 10V Output

Item Specification
Input DC 0–1mA …… 0–5A
Output DC (0)4–20mA
Accuracy 0.2%
Input Impedance (R) Ri=0.05V/Ix (Ix = measured current)
Linear Range 0–120% of nominal input
Responding Time 150ms
Over Load Capacity 10 times of nominal input, for 5 seconds
Maximum Load 6–12V
Static Current 17mA
Auxiliary Power +12VDC, +24VDC
Isolation Voltage ≥2500VDC, for 1 minute
Output Ripple <10mV
Drifting by Temperature 200×10⁻⁶/℃
Ambient Temperature -10℃~+50℃
Mounting DIN Rail 35mm Mount