LCD Display Multi Circuit Meter

LCD Display Multi Circuit Meter

WB5110-D Multifunctional Harmonic Meter is a multifunctional electric panel meter features with integrated functions of programmable of measurement parameters,LED display, digital communication , relay measurement & control and analogue measurement.
Send Inquiry
Description
Technical Parameters

WB5110-D Multifunctional Harmonic Meter is a multifunctional electric panel meter features with integrated functions of programmable of measurement parameters,LED display, digital communication , relay measurement & control and analogue measurement. 

It measures and analysis the Voltage , Current, Active Power, Reactive Power, Apparent Power, Power Factor, Frequency, Active Energy, Reactive Energy, Four-quadrant Energy, Time-period Energy, Monthly Energy, Harmonic Distribution (2-31 times) of voltage and current, Total harmonic distribution (THD) of voltage and current, Unbalanced degree of current and voltage, Positive sequence current and voltage, Negative sequence of voltage and current, Zero sequence of voltage current, Current K coefficient, Voltage peak-coefficient, Harmonic wave-factor, etc.  It also records the event of Maximum (minimum) value, lacking phase / over voltage and programming etc.

 

Technical Datasheets

Measurement System

Single Phase;

3-Phase 3-Wire;

3-Phase 4-wire;

V

Voltage

Rated Input

AC 57.7V,100V,220V,380V,500V;

Over Load

1.2 times of nominal input continuous;

2 times of nominal input for 5 seconds;

Power Consumption

< 2VA(each phase)

 

Accuracy

0.5 %, RMS sensing


Current

I

Rated Input

AC 1A,5A;

Over Load

1.2 times of nominal input continuous;

10 times of nominal input for 5 seconds;

Power Consumption

< 1VA( each phase)

Accuracy

0.5%, RMS sensing


Power

p

Active Power: Accuracy: 0.5%;

Reactive Power: Accuracy: 1%;


Energy


Active Energy: Accuracy 1%;

Reactive Energy: Accuracy 2%;


Harmonic


Measurement of harmonic wave to 31st , B Grade;

Frequency

Frequency: 45Hz – 65Hz,   Resolution: 0.01

Data Updating

Data updating ≤1s

Communication Protocol

ModBus-RTU Protocol

RS 485 Interface

Baud Rate:

1200bps /2400bps / 4800bps / 9600bps / 19200bps / 38400bps / 57600bps optional;

 

Galvanic isolation betweent RS485 interface and Input and Auxiliary power supply;

 

Plug-In Functional Module

 

Relay Output

Two- Channels Relay Output;

Contact Point Capacity: AC 250V/2A; DC 30V/2A

Alarm thresh-hold value, postponed time and switching gap can be programmed through RS485 Interface and press buttons;

 

Galvanic isolation between RS485 Interface, signal input terminal and Auxiliary power supply;

Analogue Output

Load Impedance: ≤500Ω;

Accuracy: 0.5%

Output : DC0~20mA; 4~20mA Optional;

Galvanic isolation between output terminal and input terminal and Auxiliary power supply;

Relay Input

Passive Dry Contact Signal Input;

Analogue Input

Input: DC0~20mA; 4mA~20mA; optional

Accuracy: 1%;

Energy Pulse Output

Two- Chnanels pulse output;

The width of pulse : 80ms

Passive Optical Coupler Set Electrode Output;

Auxiliary Power Supply

Voltage Range

85V~265V ac; 45-65Hz,

100-300V dc;

Power Consumption

<10VA、6W

ESD Anti-Interference Grade: 4

Transient   Pulse Anti-Interference Grade: 2

Surge   Immunity: 4

Insulation Strength:  AC 2.5kV,1minnte;

Insulation Impedance :>100MΩ

Temperature

Operating Temperature: -10~55℃;   Storage: -25~70℃

Relative Humidity

≤93%RH, None Condensation, None Corrosive

Attitude

≤2500m

Panel Dimensions

92×92mm

Overall Dimensions

96×96mm

Display

Segmented LED

1. Outline Drawing

1.1 Outline and Installation Size (unit: mm)

LCD Display Multi MeterLCD Display Multi Circuit Meter for sale

Graphic 1: Outline Size Drawing

Wiring

Please make sure the right wiring before add power on this meter.

If the wiring diagrams of operation manual differ from the meter shell shows, please follow the wiring diagrams from the meter shell.

2

Channel - 1                   Graphic 2 Main Part Terminals            Channel-4

2.2.1 Terminals Instruction

No. of

Terminals

Identificaqtion

Definiton


No. of   Terminals

Identification

Definition

1

L/+

Supply +


2

N/-

Supply -

11

Ua

Phase-A   voltage


12

Ub

Phase-B   voltage

4

Ia+

Phase-A   current In

13

Uc

Phase-C   voltage

5

Ia-

Phase-A   current Out

14

Un

Neutral   voltage

6

Ib+

Phase-B   current In


7

Ib-

Phase-B   current Out

58

RSA

RS485 (+)

8

Ic+

Phase-C   current In

59

RSB

RS485 (-)

9

Ic-

Phase-C   current Out



Applications:

   Railway signal centralized monitoring system;

   High-speed rail track signal intelligent equipment;

   Railway switch system;

   Railway disaster prevention and safety monitoring system;

   Locomotive and vehicle electrical integrated cabinet;

   Locomotive inverter power supply, traction power supply.


Hot Tags: LCD Display Multi Circuit Meter, China, suppliers, factory, price, RS485 Communication DC Energy Meter, RS485 Communication Output Digital Display Meter