Current transformer is a special transformer. Its function is to turn large current into standard small current. It works with measuring instruments, measuring instruments, relays and other equipment. This can play the role of expanding the measuring range of the instrument and improving the reliability and safety of the circuit.
The rated current of the secondary side of the current transformer is 5A or 1A, and generally 5A is selected. The commonly used transformation ratios for measuring current transformers are 5/5, 10/5, 15/5, 20/5, 25/5, 30/5, 40/5, 50/5, 75/5, 100/5, 150 / 5, 200/5, 250/5, 300/5, 400/5, 500/5, 600/5, 750/5, 800/5, etc., how to choose the transformation ratio of the current transformer correctly?
The "Code for the design of electrical measuring instruments and devices for electrical installations" stipulates that "the selection of the measuring range of pointer measuring instruments should ensure that the rated value of the electrical equipment is indicated at 2/3 of the scale of the instrument." According to this specification, we can use the following The formula selects the transformation ratio N of the current transformer.
In this formula, I is the maximum load current of the circuit, 0.7 means that the indication at the maximum load current is at 70% of the instrument panel, and 5 is the secondary rating of the current transformer
Current value. Then according to the calculated transformation ratio value, select the transformation ratio of the corresponding current transformer. For example, if I is 50A, N = 14.29 can be obtained according to the calculation formula, so the current transformer with 75/5 transformation ratio is selected.